DGX B300 vs DGX B200 vs HGX B300 servers: what differs and which to choose

Eurokommerz, Vienna, since 2006: Private AI/ML · IT Managed Services · Enterprise Training · AI Hardware & Software

IN BRIEF
  • The B300 (Blackwell Ultra) carries 288 GB of HBM3e per GPU against 180 GB in the DGX B200; NVIDIA lists up to 8 TB/s of memory bandwidth and 1.8 TB/s of NVLink per GPU for both, 14.4 TB/s of NVLink per eight-GPU system
  • NVIDIA’s HGX table gives both systems 144 PFLOPS of sparse FP4, but 108 PFLOPS dense for the B300 against 72 for the B200; FP8 (72 PFLOPS) and BF16 (36 PFLOPS) are the same, both printed as sparse
  • The B300 has twice the attention throughput of the B200 but only 10 TFLOPS of FP64 per system against 296, and 3 POPS of INT8 against 72, so double-precision codes belong on other GPUs
  • The DGX B300 moves from eight ConnectX-7 at 400 Gb/s to eight ConnectX-8 at 800 Gb/s, needs inlet air of 30 °C or less instead of 35 °C, and comes in an AC version (168 kg) and a DC busbar version (123 kg)
  • A DGX B300 is NVIDIA’s own 10U system with DGX OS and three years of NVIDIA support; an HGX B300 server has the same GPU figures in a manufacturer’s chassis, with the manufacturer’s processors, memory, cooling and support

Supplied by Eurokommerz: NVIDIA DGX B300  Check price and availability →

DGX B300 vs DGX B200: what differs

The DGX B300 and the DGX B200 are both NVIDIA systems with eight SXM GPUs, two NVLink switches and 14.4 TB/s of aggregate NVLink bandwidth in 10U. In a B300 vs B200 comparison, each B300 (Blackwell Ultra) carries 288 GB of HBM3e against 180 GB per GPU in the DGX B200, delivers 50 per cent more dense FP4 throughput and, on NVIDIA’s rating, twice the attention throughput. The DGX B300 moves the cluster network from ConnectX-7 at 400 Gb/s to ConnectX-8 at 800 Gb/s per GPU, and its GPUs give up most of the FP64 and INT8 throughput. HGX B300 vs DGX B300 is a separate question: NVIDIA prints the same GPU figures for both, but an HGX B300 server is built by a server manufacturer, with its own processors, memory, cooling and support.

SPECIFICATIONBLACKWELL B200BLACKWELL ULTRA B300
HBM3e per GPU180 GB in the DGX B200288 GB
GPU memory per system1,440 GB2.1 TB listed; 8 × 288 GB = 2.3 TB
HBM bandwidth8 TB/s per GPU, 64 TB/s per DGX B2008 TB/s per GPU; 62 TB/s per DGX B300 in its datasheet
FP4 Tensor, sparse / dense144 / 72 PFLOPS144 / 108 PFLOPS
FP8 Tensor, sparse72 PFLOPS72 PFLOPS
FP16 and BF16, sparse36 PFLOPS36 PFLOPS
INT8 Tensor, sparse72 POPS3 POPS
FP64 and FP64 Tensor296 TFLOPS10 TFLOPS
Attention (SFU EX2) per GPU5 TeraExponentials/s10.7 TeraExponentials/s
NVLink per GPU1.8 TB/s1.8 TB/s
Cluster network per GPUConnectX-7, 400 Gb/sConnectX-8, 800 Gb/s
Compute capability10.010.3

Per eight-GPU system unless marked per GPU. NVIDIA HGX platform page (updated 30 September 2026), DGX B200 and DGX B300 product pages (updated 16 and 15 October 2026), DGX B300 user guide (5 October 2026); attention and bandwidth per GPU from NVIDIA’s Blackwell Ultra technical blog (22 August 2025) and the DGX B300 datasheet (February 2026); compute capability from NVIDIA’s CUDA GPU list, read 16 October 2026.

B300 vs B200 performance: dense FP4, FP8 and attention

NVIDIA prints most Tensor Core figures with sparsity, and its footnote says “Dense is ½ sparse spec shown.” For FP4 the HGX table gives both figures, and the sparse one is the same for both systems, 144 PFLOPS. The dense figure differs: 108 PFLOPS for eight B300 against 72 for eight B200, or 13.5 and 9 PFLOPS per GPU by our division. NVIDIA’s Blackwell Ultra blog gives the chips 15 and 10 PFLOPS of dense NVFP4, the same ratio of 1.5. NVFP4 checkpoints do not use the 2:4 structured sparsity behind the sparse figure, so compare the dense column, as our TFLOPS comparison of dense and sparse figures explains.

FP8 and BF16 are unchanged, at 72 and 36 PFLOPS of sparse throughput per system. A model served in FP8, or a training run in BF16 or FP8, gains nothing from the B300’s tensor rates on paper. NVIDIA lists up to 8 TB/s of memory bandwidth per GPU on both, so the ceiling for one user’s token rate, bandwidth divided by the bytes read per token, is about the same for a model that fits either GPU. The B300 gains where FP4 compute, attention or memory capacity limit the work: prompt processing and large batches in NVFP4, long contexts, and more concurrent sessions per GPU.

For attention, NVIDIA’s blog lists the special function units at 10.7 TeraExponentials per second on Blackwell Ultra against 5 on Blackwell, “delivering up to 2x faster attention-layer” compute. Attention grows with the context, so the gain is largest for long prompts, RAG requests with many retrieved passages and reasoning models that write long answers.

The B300 gives up double precision and INT8. NVIDIA’s HGX table lists 10 TFLOPS of FP64 per eight-GPU system against 296 for the B200, and 3 POPS of INT8 against 72. A simulation, CFD or quantum chemistry code that needs FP64 runs far slower on the newer system. Models quantised to INT8 weights and activations should be moved to FP8 on the B300, which runs at the same rate as on the B200.

DGX B200 vs DGX B300 specs: power, cooling, processors and network

On NVIDIA’s figures the two DGX models draw similar power and differ in network, weight, power distribution and inlet limit.

ASPECTDGX B200DGX B300
Processors2 × Xeon Platinum 8570, 56 cores each2 × Xeon 6776P
System memory2 TB, up to 4 TB2 TB default, up to 4 TB
Cluster network4 OSFP ports, 8 × ConnectX-7, up to 400 Gb/s8 OSFP ports, 8 × ConnectX-8, up to 800 Gb/s
Storage network2 × dual-port BlueField-3, up to 400 Gb/s2 × dual-port BlueField-3, up to 400 Gb/s
Data cache8 × 3.84 TB NVMe U.28 × 3.84 TB NVMe E1.S
System power14.3 kW max14.5 kW, 15 kW max at the 54 V busbar input (user guide); 15.1 kW PSU, 14.5 kW busbar (datasheet); ~14 kW (product page)
Power supplies6 × 3.3 kW, 5+112 × 3.2 kW, N+N, at least 6; or a DC busbar
Weight142.4 kg max168 kg with power supplies, 123 kg busbar version
Inlet air10 to 35 °C10 to 30 °C
Airflow1,550 CFM, no fan speed stated1,500 CFM, busbar version 1,350, at 70 % fan speed; up to about 2,145 CFM per system for facility design
Size10U, 897.1 mm deep10U, 904.2 mm deep
Supportthree years, Business Standardthree years, Business Standard

NVIDIA DGX B200 user guide (updated 8 September 2026) and product page (16 October 2026); DGX B300 user guide (updated 5 October 2026), product page (15 October 2026), datasheet (February 2026) and “Data Center Best Practices with DGX B300” (version 1.0, 27 February 2026).

NVIDIA offers the DGX B300 in AC/PDU and DC/busbar versions, and its product page says it is “deployable in NVIDIA MGX racks for the first time.” The lower inlet limit matters when both generations share a room, since supply air between 30 and 35 °C suits the DGX B200 but not the DGX B300. NVIDIA’s data-centre guide sizes a rack with two AC-powered DGX B300 at 39.4 kW peak and 30 kW average, so plan the power feed to the peak rather than to the nameplate figures in the table. The cluster network doubles per port, so switches, optics and cables have to be planned for 800 Gb/s. NVIDIA’s DGX SuperPOD reference architecture for the DGX B300 with AC power, updated on 2 September 2026, uses Quantum-X800 InfiniBand switching and scalable units of 72 systems. The room, floor load and power distribution for one or two systems are covered in our DGX B300 specifications and power requirements.

HGX B300 vs DGX B300: NVIDIA’s system or a manufacturer’s server

NVIDIA describes HGX as “a single baseboard with eight” Rubin, Blackwell or Blackwell Ultra SXM GPUs, and server manufacturers build their HGX B300 servers around it. The GPU figures in NVIDIA’s HGX table are the same as the DGX B300’s, and the table adds that “CPU and memory specs are defined by OEM offerings.” When NVIDIA announced Blackwell Ultra on 18 March 2025, it named Cisco, Dell Technologies, Hewlett Packard Enterprise, Lenovo and Supermicro among the companies expected to deliver servers based on it. Their HGX B300 servers differ from the DGX B300 and from each other in processors, memory, chassis height and cooling.

Supermicro’s 8U air-cooled HGX B300 server, for example, takes two AMD EPYC 9005 processors and up to 6 TB of DDR5. Its 4U version is cooled by direct liquid cooling, which Supermicro says captures up to 98 per cent of the system’s heat, and fits up to 64 GPUs in a standard 19-inch rack (press release of 9 December 2025).

ASPECTDGX B300HGX B300 SERVER
Built byNVIDIAthe server manufacturer, on NVIDIA’s eight-GPU board
GPUs and NVLink8 × B300 SXM, 2.1 TB, 14.4 TB/sthe same figures in NVIDIA’s HGX table
Processors, memory2 × Xeon 6776P, 2 to 4 TBmanufacturer’s choice, for example 2 × EPYC 9005 and up to 6 TB
Chassis, cooling10U, air-cooled, AC supplies or DC busbarper model, for example 8U air-cooled or 4U liquid-cooled
SoftwareDGX OS included; AI Enterprise and Mission Control recommendedoperating systems and drivers as the manufacturer supports them
Supportthree years of NVIDIA Business Standard supportthe manufacturer’s warranty and support terms
Cluster designDGX BasePOD and SuperPOD reference architecturesthe manufacturer’s rack and cluster designs

NVIDIA DGX B300 product page (15 October 2026) and HGX platform page (30 September 2026); Supermicro AS-8126GS-NB3RT product page, read 16 October 2026, and press release of 9 December 2025.

Choose the DGX B300 when one company should answer for the whole system, when you plan to grow along NVIDIA’s DGX BasePOD or SuperPOD reference architectures, and when you want Mission Control for cluster operations. Choose an HGX B300 server when you need AMD processors, more than 4 TB of system memory, direct liquid cooling or a lower chassis, or when your other servers already run under one manufacturer’s management tools and support contract. NVIDIA AI Enterprise is licensed per GPU on either, eight licences per system, and the DGX B300 page lists it as recommended rather than included. Our guide to buying a DGX B300 in the EU covers the order itself.

We supply the DGX B300 and HGX B300 servers per project. Before we can quote, the distribution asks us for the company, the project and the intended use, so send us those three and we check price and availability for your project.

Which to choose for inference, training, HPC and mixed fleets

For large-model inference with long contexts, the B300’s memory decides. Llama 3.1 405B in FP8 takes about 405 GB of weights at one byte per parameter. On a DGX B200 that leaves about 1 TB for KV cache before any reserve, on a DGX B300 about 1.7 TB against the 2.1 TB NVIDIA lists, so the B300 holds about 60 per cent more concurrent long sessions. A 70B model in BF16, about 141 GB, fits one B200 GPU with under 40 GB to spare and one B300 GPU with more than 100 GB, which changes how many conversations each copy serves.

For training and fine-tuning in BF16 or FP8 the tensor rates are equal, so the B300’s advantage is memory per GPU, for larger batches or fewer GPUs per model shard, and 800 Gb/s per GPU between nodes. For HPC codes that need FP64, the B200 has about 30 times the B300’s rate on NVIDIA’s figures, 296 against 10 TFLOPS per system, and the H200 NVL lists 30 TFLOPS per card.

Mixed fleets work when jobs are placed by what each generation does well: FP64 and INT8 work on the B200 nodes, long-context and NVFP4 inference on the B300. NVIDIA’s CUDA list gives the B200 compute capability 10.0 and the B300 10.3, so check that the framework and container versions you run support the B300 before both share one scheduler queue.

When a PCIe server with H200 NVL or RTX PRO 6000 fits better

An eight-GPU SXM system is sized for models that must be split across GPUs at low latency and for training that exchanges gradients every step. When each model copy fits one 96 GB RTX PRO 6000 Server Edition or one 141 GB H200 NVL, a PCIe server runs one copy per card, draws 4.8 kW of GPU power with eight 600 W cards and stands in an ordinary server room. Our DGX B300 vs eight RTX PRO 6000 comparison sets the two side by side, and the RTX PRO 6000 vs H200 NVL comparison covers the choice between the two cards. The H200 NVL also suits FP64 work and bridges 2 or 4 cards over NVLink, and the RTX PRO 6000 adds graphics and virtual workstations, which the B300 lacks.

We build AI servers to order with four or eight of these cards and check the rack, power and airflow before we quote. Describe your models, their precision and your user count for a configuration and quote within one business day.

What we supply

We supply the DGX B300 and HGX B300 servers per project, on one EU contract and invoice. Before we can quote, the distribution asks us for the company, the project and the intended use, and approvals take longer than an order for cards. For workloads that fit PCIe cards, we build AI servers to order with H200 NVL and RTX PRO 6000 Server Edition cards, assembled and burn-in tested, with manufacturer warranty on every component. The cards themselves are on our professional GPU line-up, and NVIDIA AI Enterprise licences come on the same invoice.

FAQ

What is the difference between DGX B300 and DGX B200?
The DGX B300 has eight Blackwell Ultra GPUs with 288 GB of HBM3e each and the DGX B200 eight Blackwell GPUs with 1,440 GB in total, 180 GB each. The B300 has 50 per cent more dense FP4 throughput, twice the attention throughput and ConnectX-8 networking at 800 Gb/s instead of ConnectX-7 at 400 Gb/s, but far less FP64 and INT8. Both are 10U; NVIDIA rates the DGX B200 at 14.3 kW maximum and the DGX B300 at 14.5 to 15.1 kW in its user guide and datasheet, and the B300 needs inlet air of 30 °C or less instead of 35 °C.
b300 vs b200 memory: how much more does the B300 have?
Each B300 GPU carries 288 GB of HBM3e, and NVIDIA lists 2.1 TB per eight-GPU system. The DGX B200 has 1,440 GB, or 180 GB per GPU. NVIDIA lists up to 8 TB/s of memory bandwidth per GPU on both, so the B300 holds more but does not read it faster.
b300 vs b200 performance: is the B300 faster?
On NVIDIA’s figures the B300 is faster in dense FP4, 108 against 72 PFLOPS per eight-GPU system, and in attention, which NVIDIA rates at up to twice the B200. FP8 and BF16 throughput are the same on both, and memory bandwidth per GPU is about the same. In FP64 the B200 is much faster, 296 against 10 TFLOPS per system.
What is the difference between HGX B300 and DGX B300?
The DGX B300 is NVIDIA’s own complete system with two Xeon 6776P processors, 2 to 4 TB of memory, DGX OS and three years of NVIDIA support. HGX B300 is NVIDIA’s eight-GPU board, which server manufacturers build into their own servers with their own processors, memory, cooling and support. NVIDIA’s tables give both the same GPU figures.
What is an HGX B300 server?
An HGX B300 server is a manufacturer’s server built around NVIDIA’s baseboard with eight Blackwell Ultra SXM GPUs, 2.1 TB of HBM3e and 14.4 TB/s of NVLink bandwidth. NVIDIA states that CPU and memory are defined by the manufacturer. Supermicro, for example, offers an 8U air-cooled model with two AMD EPYC 9005 processors and up to 6 TB of memory, and a 4U model with direct liquid cooling.
Blackwell Ultra vs Blackwell: which is better for HPC and FP64?
Blackwell is far stronger in double precision: NVIDIA lists the HGX B200 at 296 TFLOPS of FP64 and the HGX B300 at 10 TFLOPS. Blackwell Ultra is built for AI inference and training in low precision, with more memory, more dense FP4 throughput and faster attention. Simulation and solver codes that need FP64 belong on the B200 or on GPUs such as the H200 NVL, which lists 30 TFLOPS per card.

Send us the company, the project and its intended use, the models with their precision and context length, and where the systems would run. We reply within one business day: for the DGX B300 and HGX B300 servers we check price and availability for your project, and for PCIe servers we send a configuration and quote.