HGX B200 power consumption and cooling: kW, feeds, rack and room for one or two servers
Eurokommerz, Vienna, since 2006: Private AI/ML · IT Managed Services · Enterprise Training · AI Hardware & Software
- NVIDIA rates each B200 GPU on the HGX board as configurable up to 1,000 W, which is 8 kW for eight GPUs alone by our multiplication
- NVIDIA gives its own DGX B200 a maximum of 14.3 kW; Supermicro, ASUS and Gigabyte publish no system power figure for their HGX B200 servers, so we plan them in the same class until a measurement on the delivered system gives a value
- The power supplies differ per model: six 6,600 W as 3+3 on the Supermicro SYS-822GS-NBRT and twelve 3,000 W as 6+6 on Gigabyte's 8U models
- By our arithmetic one server in the 14.3 kW class needs a 400 V 32 A three-phase feed on each side, and two servers put about 28.6 kW into one rack
- Air-cooled versions are 8U or 10U and weigh 91.6 to 142.4 kg; liquid-cooled 4U versions move up to 87 per cent of the heat into the liquid, by Supermicro's figure
Supplied by Eurokommerz: HGX B200 servers Request a price →
How much power an HGX B200 server draws
An HGX B200 server is planned at about 14 kW at full load, because that is the nearest figure NVIDIA publishes. NVIDIA's HGX B200 carbon footprint summary (July 2025) gives each B200 GPU a maximum TDP "configurable up to 1000 W", so the eight GPUs alone account for up to 8 kW by our multiplication, and NVIDIA's DGX B200 user guide (updated 17 October 2026) rates the whole DGX B200, NVIDIA's own system on the same board, at "14.3 kW max". None of the server makers whose pages we read on 27 November 2026 publishes a system power figure for its HGX B200 model, so the DGX figure is the nearest published reference.
| ITEM | FIGURE | DOCUMENT |
|---|---|---|
| B200 GPU on HGX B200 | configurable up to 1,000 W | NVIDIA carbon footprint summary |
| Eight GPUs, GPU power only | up to 8 kW | our multiplication |
| Supermicro SYS-822GS-NBRT | 1000W TDP per GPU, air-cooled | Supermicro product page |
| DGX B200, whole system | 14.3 kW max | DGX B200 user guide |
| Makers' HGX B200 servers | no system figure published | makers' pages |
NVIDIA HGX B200 PCF summary (footer "Jul25"), NVIDIA DGX B200 user guide (updated 17 October 2026), Supermicro product page SYS-822GS-NBRT, all read 27 November 2026.
The gap between 8 kW and 14.3 kW is the rest of the system: two processors, memory, drives, eight network cards and two DPUs, fans and the losses of the power supplies. That share depends on the maker's design, which is why we plan an HGX B200 server at the 14.3 kW of the DGX B200 and size the feeds to the rating of the power supplies the maker specifies, until a measurement on the delivered system gives a real value. For comparison, NVIDIA's DGX H100 user guide gives the previous generation 10.2 kW maximum; replacing such a system is covered in replacing an 8-GPU H100 SXM server.
We supply HGX B200 servers per project and choose the model and its power supplies to fit the feeds at your rack. For an order we need the end user's company, the installation site and the intended use; the server maker and NVIDIA review the project before they confirm it, as our guide to the end-user certificate for NVIDIA GPUs explains. Send us the voltage, the feeds and the outlets at the rack position, and we reply with a configuration that fits them.
Power supplies per HGX B200 server model
Every HGX B200 server has redundant supplies, but the makers split the power differently. The last column adds up the supplies that carry the server on their own, the N in N+N or N+1, at their nominal rating.
| MODEL | SUPPLIES | REDUNDANCY | N SUPPLIES, RATED |
|---|---|---|---|
| Supermicro SYS-822GS-NBRT | 6 × 6,600 W | 3+3 | 19.8 kW |
| Supermicro AS-A126GS-TNBR | 6 × 5,250 W | 3+3 | 15.75 kW |
| Supermicro SYS-422GS-NBRT-LCC | 4 × 6,600 W | 2+2 | 13.2 kW |
| ASUS ESC NB8-E11 | 6 × 3,000 W | 5+1 | 15 kW |
| Gigabyte G893/G894, 8U | 12 × 3,000 W | 6+6 | 18 kW |
| Gigabyte G4L3-SD1-LAX5 | 8 × 3,000 W | 4+4 | 12 kW |
| NVIDIA DGX B200 | 6 × 3.3 kW | 5+1 | 16.5 kW |
makers' product pages, datasheets and technical guides, read 27 November 2026; last column our arithmetic (N × nominal rating), not a power draw.
The nominal rating holds only in part of the voltage range. Supermicro's 6,600 W supply delivers 6,600 W at 239 to 240 V, 6,500 W at 230 to 238.9 V and 5,900 W at 200 to 207.9 V, so three of them give 19.5 kW on a 230 V supply by our arithmetic; the full table of voltage bands is in our article on the Supermicro SYS-822GS-NB3RT, whose B300 chassis uses the same supplies. Gigabyte rates its 3,000 W supplies at 2,900 W from 200 to 220 V, 3,002.4 W from 220 to 240 V and 1,450 W from 115 to 127 V. NVIDIA rates each DGX B200 supply at 3,300 W at 200 to 240 V and 16 A. Plan every one of these servers on 200 to 240 V.
Two rows deserve a question before the order. Supermicro's liquid-cooled 4U model and Gigabyte's G4L3-SD1-LAX5 carry the server on supplies that add up to less than the DGX B200's 14.3 kW. These are different systems with their own power budgets, and the makers publish none, so ask the maker what the server draws at full GPU power and what it does when one side fails. How N+N and N+1 behave on A and B feeds is explained in PSU redundancy in GPU servers.
Feeds and circuits for an HGX B200 server
Planned at 80 per cent, as in our guide to GPU server power on 16 A, 32 A and three-phase feeds, a 230 V 32 A single-phase feed carries 5.89 kW and a 400 V 32 A three-phase feed 17.74 kW. A server in the 14.3 kW class therefore needs one 400 V 32 A three-phase feed per side by our arithmetic: with N+N supplies, each of the A and B feeds has to carry the whole server when the other fails. Two servers come to about 28.6 kW and need two such feeds per side, or a rack PDU of matching capacity.
The connectors count as much as the kilowatts. NVIDIA rates each of the six DGX B200 supplies at 16 A, the current that IEC 60320 C19 and C20 connections carry, so by our reading the system takes six outlets. Gigabyte states that the C19 cords of its twelve supplies are not included. Supermicro's 6,600 W supply is a different case: 6,500 W of output at 230 V means more than 28 A of input current by our arithmetic, more than one 16 A connection carries, and the product page names neither the inlet nor the cord. Have Supermicro confirm the number and type of power connections per supply before the PDUs are ordered.
Air-cooled 8U and 10U or liquid-cooled 4U
The same board comes in two cooling designs. Air-cooled servers are 8U or 10U high and move all the heat into the room; liquid-cooled servers fit in 4U and take most of the heat away in the coolant.
| MODEL | HEIGHT | COOLING | NET WEIGHT |
|---|---|---|---|
| Supermicro SYS-822GS-NBRT | 8U | air, 12 heavy-duty fans | 133 kg |
| Supermicro AS-A126GS-TNBR | 10U | air | 133 kg |
| ASUS ESC NB8-E11 | 10U | air, separate CPU and GPU tunnels | 121 kg, without CPU, memory, drives |
| Gigabyte G894-SD1-AAX5 | 8U | air | 91.6 kg |
| NVIDIA DGX B200 | 10U | air, 1,550 CFM | 142.4 kg max |
| Supermicro SYS-422GS-NBRT-LCC | 4U | direct-to-chip, up to 87 % to liquid | 85 kg |
| Gigabyte G4L3-SD1-LAX5 | 4U | direct-to-chip, coolant inlet up to 45 °C | not listed |
makers' product pages, datasheets and technical guides and NVIDIA DGX B200 user guide, read 27 November 2026.
Liquid cooling does not remove the room's air load. By Supermicro's own share, up to 13 per cent of the heat of its 4U model still leaves as air, by our subtraction. The liquid-cooled models also come with conditions on the rack: Supermicro describes its SYS-422GS-NBRT-LCC with "complete rack and onsite service are required" and states that complete liquid-cooled rack integration is required for purchase, and Gigabyte lists CoolIT cold plates and leak detection for the G4L3-SD1-LAX5. Facility water, coolant distribution units and the share of heat a cold plate captures are covered in our guide to liquid cooling for GPU racks.
Inlet temperature and airflow
Most air-cooled HGX B200 servers accept inlet air from 10 to 35 °C: the Supermicro and ASUS models above and the DGX B200 give that range. Gigabyte's 8U air-cooled models are the exception at 10 to 30 °C, with 8 to 80 per cent relative humidity; Supermicro lists 8 to 90 per cent, non-condensing, for the SYS-822GS-NBRT. A room that may receive a Gigabyte server is therefore planned for 30 °C supply air.
NVIDIA states 1,550 CFM of airflow for the DGX B200. The planning rule in our guide to GPU rack power and cooling, about 160 CFM per kW at an 11 °C rise, gives about 2,290 CFM for 14.3 kW by our arithmetic. The same heat in less air means a larger temperature rise across the server than the rule assumes, so the hot aisle runs warmer; we read NVIDIA's figure as its fan design and plan the room with the rule. Blanking panels in empty rack units keep that exhaust away from the intakes.
Weight, depth and floor
The depth of an HGX B200 server varies by almost 150 mm between models: 843.28 mm for Supermicro's AS-A126GS-TNBR, 885 mm for the ASUS ESC NB8-E11, 923 mm for Gigabyte's 8U models, 950 mm for the SYS-822GS-NBRT and 991.4 mm for Supermicro's 4U liquid model. NVIDIA's DGX B200 is 897.1 mm. A rack planned for one model is not automatically deep enough for another, so the rack depth and the rail range belong in the enquiry.
Supermicro gives the SYS-822GS-NBRT a gross weight of 155 kg in a package of 670 × 730 × 1,280 mm. Two of these servers in one rack add 266 kg net by our arithmetic, before rack, PDUs and cabling. Most of the published weights are net weights of the chassis or of a stated configuration, so ask for the weight of the configured system. The floor rating comes from the building, and the way from the loading bay to the rack has to carry the packed weight; our site survey for GPU servers lists what to measure.
One or two HGX B200 servers in the room
One air-cooled HGX B200 server in the 14.3 kW class exceeds a 10 kW rack on its own, as our article on air-cooled AI servers in a 10 kW rack shows for the DGX B200. Two servers in one rack, about 28.6 kW by our arithmetic, sit in the 15 to 40 kW band for which our rack guide plans hot and cold aisle containment. Supermicro's SuperCluster datasheet for the air-cooled 10U B200 systems (February 2025) places four nodes, 32 GPUs, in a rack; four servers in the 14.3 kW class come to about 57.2 kW by our arithmetic, above the roughly 50 kW at which our liquid cooling guide sees liquid as the practical route.
In our judgement, for most first projects with one or two servers, air cooling in a contained aisle with three-phase feeds is enough, and the 4U liquid-cooled models are the choice where the facility already has a water loop or the rack has to hold more. Whether an HGX B200 server or a different system suits the room at all is part of the comparison in HGX B200 now or HGX B300 later, and the order itself is described in our guide to buying an HGX B200 server. The component list behind the power figures is in HGX B200 server specs and configuration.
Your data-centre staff or the colocation provider rack and connect the server; we do not work on site, and hardware service on site comes from the server maker as configured in the quote. We match the model and its supplies to your room before we quote; tell us the rack position, its kW limit and the supply-air temperature with the end user, the site and the intended use, and we propose the configuration.
FAQ
How much power does an HGX B200 server use?
How many kW does a B200 rack need?
Does the HGX B200 need liquid cooling?
Which power supplies does an HGX B200 server have?
What power feed does an HGX B200 server need?
How heavy is an HGX B200 server?