Liquid-cooled HGX B200 and B300 servers in 4U: models, heat to liquid and the room
Eurokommerz, Vienna, since 2006: Private AI/ML · IT Managed Services · Enterprise Training · AI Hardware & Software
- Supermicro lists the SYS-422GS-NBRT-LCC and AS-4126GS-NBR-LCC on HGX B200 and the SYS-422GS-NB3RT-LCC and -ALC on HGX B300; Gigabyte's G4L3-SD1-LAX5 is a 4U HGX B200 server with CoolIT cold plates and leak detection
- Supermicro's pages credit the cold plates with up to 87 per cent of the heat (LCC) and up to 95 per cent with the maximum configuration (DLC-2 on the -ALC); the rest still leaves as air through the remaining fans
- Gigabyte limits the coolant inlet to 45 °C and, above 50 per cent relative humidity, requires it to be warmer than the dry-bulb temperature; no model page we read states CDU capacity, facility water temperature or flow
- The Supermicro 4U HGX model pages we read carry the note "complete rack and onsite service are required"; Supermicro's SuperCluster datasheet puts eight such servers, 64 GPUs, in one rack against four air-cooled 10U servers
- We supply HGX B200 and HGX B300 servers per project; for an order we need the end user's company, the installation site and the intended use
Supplied by Eurokommerz: HGX B200 servers Request a price →
Which liquid-cooled 4U HGX servers the makers list
Liquid-cooled HGX B200 and HGX B300 servers fit eight GPUs into 4U by putting direct-to-chip cold plates on the hottest parts: the GPUs and, where the pages name them, the NVSwitch chips and the processors. Supermicro lists the SYS-422GS-NBRT-LCC and the AS-4126GS-NBR-LCC on HGX B200 and the SYS-422GS-NB3RT-LCC and SYS-422GS-NB3RT-ALC on HGX B300, with up to 87 or 95 per cent of the heat captured by the cold plates as their pages print it; Gigabyte's G4L3-SD1-LAX5 uses CoolIT cold plates and accepts coolant up to 45 °C. None of these model pages states what the facility has to provide in CDU capacity, water temperature or flow.
| MODEL | BOARD | PROCESSORS | TO LIQUID | SUPPLIES |
|---|---|---|---|---|
| Gigabyte G4L3-SD1-LAX5 | HGX B200 | 2 × 5th/4th Gen Xeon, 350 W | not printed | 8 × 3,000 W, 4+4 |
| Supermicro SYS-422GS-NBRT-LCC | HGX B200 | 2 × Xeon 6700P, 350 W | up to 87 % | 4 × 6,600 W, 2+2 |
| Supermicro AS-4126GS-NBR-LCC | HGX B200 | 2 × EPYC 9005/9004 | not printed | 4 × 6,600 W, 2+2 |
| Supermicro SYS-422GS-NB3RT-LCC | HGX B300 | 2 × Xeon 6700P, 350 W | up to 87 % | 4 × 6,600 W, 2+2 |
| Supermicro SYS-422GS-NB3RT-ALC | HGX B300 | 2 × Xeon 6700P, 350 W | up to 95 %, max config | 4 × 6,600 W, 2+2 |
Supermicro product and datasheet pages of the four models and Gigabyte's G4L3-SD1-LAX5 page (©2026, no revision dates), read 27 November 2026.
The makers list more 4U liquid-cooled models whose specifications we have not read. Supermicro's brochure "NVIDIA Blackwell Solutions" (December 2025) adds the SYS-422GA-NBRT-LCC with Xeon 6900 and the SYS-421GE-NBRT-LCC with 5th or 4th Gen Xeon on B200, and the AS-4126GS-NB3RT-LCC on B300, all with four 6,600 W supplies as 2+2. Gigabyte's model list names the G4L4-SD1 and G4L4-AD1 (Xeon 6) and the G4L3-ZD1 (EPYC) on B200, and the G4L4-SD3, G4L4-AD3 and G4L4-ZD3 on B300. ASUS names only the air-cooled ESC NB8-E11 as its HGX B200 system, and its HGX B300 model in our research, the XA NB3I-E12, is air-cooled as well.
We supply HGX B200 servers and HGX B300 servers from Supermicro, ASUS, Gigabyte, HPE and Lenovo per project, the liquid-cooled models included. For an order we need the end user's company, the installation site and the intended use, and the server maker and NVIDIA review the project before they confirm it, as our guide to the end-user certificate for NVIDIA GPUs explains. Send us the number of servers and what your facility offers on the water side, and we reply with the models that fit it.
What the cold plates cool and what stays on air
The pages say where the plates sit. Supermicro's SYS-422GS-NB3RT-LCC page speaks of "cold plates to the highest TDP components (CPUs, GPUs, and NVSwitches)". Gigabyte lists separate CoolIT cold plate loops for the CPUs, the GPUs and the NVSwitch, with their part numbers, and calls the design a "CPU+GPU direct liquid cooling solution with leak detection". None of the pages names cold plates for memory, drives, network cards or power supplies, so these stay on air.
Fans remain in every model, fewer and smaller than in the air-cooled versions:
| MODEL | FANS AS PRINTED |
|---|---|
| Supermicro SYS-422GS-NBRT-LCC | 4 × 80 mm |
| Supermicro AS-4126GS-NBR-LCC | up to 5 × 6 cm, with air shroud |
| Supermicro SYS-422GS-NB3RT-LCC | "4x 80cm heavy duty fans" (80 mm meant) |
| Supermicro SYS-422GS-NB3RT-ALC | 6 × 80 mm |
| Gigabyte G4L3-SD1-LAX5 | 4 + 4 board and PCIe fans, 4 × 60 mm GPU tray |
makers' model pages, read 27 November 2026; the "80cm" is printed so on Supermicro's page.
Gigabyte's figures make the change visible. Its 4U liquid model has four 60 × 60 × 38 mm fans in the GPU tray, where its air-cooled 8U B200 and B300 servers have fifteen of 80 × 80 × 80 mm, and keeps two 60 × 60 × 56 mm and two 60 × 60 × 76 mm fans on the board and four 80 × 80 × 56 mm fans for the PCIe area.
The share left to air follows from the capture figures. At up to 87 per cent to liquid, at least 13 per cent of the heat leaves as air by our subtraction, and at up to 95 per cent at least 5 per cent; Supermicro ties the 95 per cent to "max config", and neither figure comes with the conditions it was measured under. All five models list an operating range of 10 °C to 35 °C for the room air, Gigabyte with 8 to 80 per cent relative humidity. Gigabyte adds: "The ambient temperature is limited to 30°C when NVIDIA® BlueField®-3 DPU/SuperNIC™ are installed." A cluster that uses BlueField-3 SuperNICs in this server therefore needs supply air of 30 °C or less.
What the room needs: CDU, facility water and leak detection
The model pages leave the facility side open. Supermicro's pages for the four models above print no CDU, no facility water temperature, no flow rate and no connector type, and the -ALC page does not define "ALC". Gigabyte's page names no flow rate, CDU, facility water or quick-disconnect type either. It gives one condition for the coolant at the server: "To ensure system stability and prevent condensation, when the relative humidity exceeds 50%, the coolant inlet temperature must be higher than the dry-bulb temperature and it should not exceed 45°C."
That sentence concerns the coolant entering the server. Between that loop and the building's water sits a coolant distribution unit, and what the facility water may be depends on that unit, which the model pages do not name. Supermicro describes one at rack level. Its SuperCluster datasheet for the 4U liquid-cooled B200 systems (February 2025) lists a CDU of 250 kW per unit with "redundant PSU and dual hot-swap pumps", four CDUs for a 32-node scalable unit and eight for 96 nodes, and a "Vertical Cooling Distribution Manifold (CDM)" so that "horizontal manifolds no longer occupy valuable rack space". It gives no facility water temperature, no flow and no total kW per rack, and it does not say whether the CDU sits in the rack or in the row. Four CDUs for 32 nodes is one per eight servers by our division.
Leak detection appears only on Gigabyte's page among those we read, with a leak sensor board, the CNBG72. ASHRAE's water classes, the flow per kilowatt and the CDU types are the subject of our guide to liquid cooling for GPU racks, which this article does not repeat. For a project these points have to be answered by the facility team and the server maker before a model is chosen:
- the CDU: in the rack or in the row, its capacity and its redundancy;
- the facility water: supply temperature, flow and water quality at the rack position;
- the secondary loop: coolant type, connectors and manifolds, and who fills and commissions it;
- leak detection and drainage under the manifolds;
- the air side: room cooling for the remaining heat, at 30 °C or less where BlueField-3 cards sit in a Gigabyte G4L3.
We plan the server lines of the quote around these answers; tell us the CDU capacity, the water temperature and the rack positions you have, and we come back with the matching configuration.
Rack integration comes with the purchase at Supermicro
Supermicro sells its 4U HGX models as part of a rack. The SYS-422GS-NBRT-LCC is described as "DP Intel 4U Liquid-Cooled System with NVIDIA HGX B200 8-GPU (complete rack and onsite service are required)", and its page adds that complete liquid-cooled rack integration is required for purchase. The AS-4126GS-NBR-LCC says "Rack solution and onsite service required for purchase." The two B300 models carry the same bracket in their titles, and our review of the Supermicro SYS-822GS-NB3RT quotes the -ALC page with the same rack integration sentence.
The pages do not say what the onsite service covers. By these statements Supermicro sells these 4U liquid-cooled models only with its complete liquid-cooled rack integration and its onsite service, so in such a project the rack integration and the onsite service are Supermicro's. We quote the servers per project and clarify Supermicro's conditions with you. We do no work on site ourselves; hardware service on site comes from the server maker as configured in the quote. On request we pre-install the operating system, drivers, CUDA and a container runtime, with remote setup by our engineering partner Vixen.UNO.
Density per rack: 4U liquid against 8U and 10U air
Density is the main reason for these servers. Supermicro's SuperCluster datasheet for 4U liquid-cooled B200 systems lists "8x SYS-422GA-NBRT-LCC / AS -4126GS-NBR-LCC / SYS421GA-NBRT-LCC per rack" and "64x NVIDIA HGX B200 GPUs per rack", in 48U racks of 800 × 1,400 mm for a 32-node unit of five racks and 52U racks of the same footprint for 96 nodes in nine. The SYS-422GS-NBRT-LCC on Xeon 6700P is not in that list. The same maker's SuperCluster datasheet for air-cooled 10U B200 systems places four nodes, 32 GPUs, in a rack, and our B300 review cites Supermicro's 48U rack for four 8U SYS-822GS-NB3RT, again 32 GPUs.
| ITEM | 4U LIQUID | 10U AIR |
|---|---|---|
| Servers per rack | 8 | 4 |
| GPUs per rack | 64 | 32 |
| Rack units for servers | 32U | 40U |
| Net server weight per rack | 736 kg | 532 kg |
Supermicro SuperCluster datasheets for 4U liquid-cooled and 10U air-cooled B200 systems (February 2025); rack units and weights our arithmetic, with the AS-4126GS-NBR-LCC at 92 kg and the AS-A126GS-TNBR at 133 kg net.
No maker publishes the power a liquid-cooled HGX server draws. The supplies set a ceiling: in a 2+2 layout the server has to run on two supplies when one side fails, so with four 6,600 W supplies the redundant load stays within 13.2 kW at the nominal rating, by our reasoning. For eight such servers that is at most about 105.6 kW per rack, of which, at 87 per cent capture, about 91.9 kW would go to the liquid and about 13.7 kW to the room air, by our estimate. These are upper bounds from the supply ratings and not power figures; the measurement on the delivered system decides. Gigabyte's four 3,000 W supplies on the N side give 11.6 kW at 200 to 220 V and 12.0 kW at 220 to 240 V by our arithmetic, and its C19 cords are not included. The supply tables of all HGX B200 models are in our guide to HGX B200 power and cooling in the data centre.
Depth needs checking per model. Supermicro prints 991.4 mm for the SYS-422GS-NBRT-LCC and the -ALC, 895.35 mm for the AS-4126GS-NBR-LCC and 896.8 mm for the SYS-422GS-NB3RT-LCC, a figure our B300 review questions because the inch value on Supermicro's pages converts to 991.4 mm. Gigabyte gives 447 × 175.5 × 901 mm for the G4L3-SD1-LAX5 and no weight. The weights Supermicro prints range from 84.6 kg net for the B300 -LCC to 101 kg for the -ALC.
When a 4U liquid-cooled HGX server is the right choice
The liquid-cooled models make sense where the facility already runs a water loop with CDU capacity at the rack positions, or where the rack has to hold more than 32 GPUs. They also suit sites whose room air cannot take a whole air-cooled server: by the capture figures above, the air share of a 4U server is a small fraction of its heat. For one or two servers in an existing room without water, the air-cooled 8U and 10U versions avoid the rack project, as our power and cooling guide concludes; the Supermicro SYS-822GS-NBRT is the air-cooled sibling of the SYS-422GS-NBRT-LCC.
The software is the same on both cooling designs: driver, Fabric Manager and the NVLink checks are in our guide to HGX B200 driver install and Fabric Manager setup. The makers' air-cooled models side by side are in our comparison of HGX B200 and B300 servers from Supermicro, ASUS and Gigabyte. For budgeting GPUs and licences, companies can request our current NVIDIA price list.
FAQ
Is there a liquid-cooled HGX B200 server?
What is the Supermicro SYS-422GS-NBRT-LCC?
How much heat goes to the liquid in a 4U HGX server?
What water temperature does a liquid-cooled B200 server need?
Do I need a CDU for a liquid-cooled HGX server?
How many liquid-cooled HGX B200 servers fit in one rack?