Power capping on HGX B200 and B300 servers: GPU limits, system budgets, power profiles
Eurokommerz, Vienna, since 2006: Private AI/ML · IT Managed Services · Enterprise Training · AI Hardware & Software
- A B200 or B300 GPU takes its power limit from three sources, the VBIOS, nvidia-smi on the host and SMBPBI out-of-band, and NVIDIA's DGX B200 guide states that the GPU applies "the most conservative policy"
- NVIDIA's example Redfish output for an HGX baseboard GPU shows an allowable range of 200 to 1,000 W and a default set point of 700 W; NVIDIA rates the B200 as configurable up to 1,000 W, and the makers give 1,100 W for the B300
- On the DGX B200 and DGX B300 a whole-system budget is set through the BMC with ipmitool; in NVIDIA's example a 6 kW system cap lowers each GPU's set point from 700 to 562 W
- NVIDIA's power profiles for the B200 report power savings of up to 15 per cent for at most 3 per cent performance loss; the makers' pages for their HGX B200 and B300 servers describe no system power cap
- A cap lowers the draw but not what feeds and breakers must carry; Supermicro prints 15 kW at full load for its 8U HGX B300 node and NVIDIA 14.3 kW maximum for the DGX B200
Supplied by Eurokommerz: HGX B200 servers Request a price →
What power capping does on an HGX B200 or B300 server
Power capping on an HGX server limits each GPU's power, and on some systems the whole server's, below what the hardware can draw. NVIDIA's DGX B200 user guide, chapter "Managing Power Capping" (updated 17 October 2026), names three sources for a GPU's limit, the VBIOS, the nvidia-smi tool on the host and SMBPBI out-of-band, and states: "The GPU Performance Monitoring Unit (PMU) selects the most conservative policy to cap a system's power consumption." Its example Redfish output shows a GPU limit range of 200 to 1,000 W with a default set point of 700 W.
A cap is the tool for a rack position that is smaller than the server, for a contracted kW budget at a colocation site, or for energy per job. It does not change what the feeds have to carry: NVIDIA rates its DGX B200 at 14.3 kW maximum, and Supermicro prints 15 kW at full load for each SYS-822GS-NB3RT node on its HGX B300 rack page, read 27 November 2026.
We supply HGX B200 servers and HGX B300 servers from Supermicro, ASUS, Gigabyte, HPE and Lenovo per project. For an order we need the end user's company, the installation site and the intended use, and the server maker and NVIDIA review the project before they confirm it, as our guide to the end-user certificate for NVIDIA GPUs explains. Send us the kW limit of your rack position and the workload, and we reply with a configuration and the limits that fit it.
B200 and B300 power limits: what NVIDIA and the makers publish
| ITEM | VALUE | DOCUMENT |
|---|---|---|
| B200 on HGX B200 | configurable up to 1,000 W | NVIDIA HGX B200 PCF summary |
| B300 on HGX B300 | 1,100 W per GPU | Supermicro, other makers |
| AllowableMin, example | 200 W | NVIDIA DGX B200 guide |
| AllowableMax, example | 1,000 W | NVIDIA DGX B200 guide |
| DefaultSetPoint, example | 700 W | NVIDIA DGX B200 guide |
| Typical draw, floor | about 300 W, cap down to 200 W | NVIDIA DGX B200 guide |
NVIDIA HGX B200 product carbon footprint summary (footer "Jul25"); Supermicro's Blackwell overview ("eight 1100W HGX B300 GPUs"); NVIDIA DGX B200 user guide, "Managing Power Capping", updated 17 October 2026; read 27 November 2026.
The three example values are NVIDIA's sample output, not a statement of the default on every HGX server as delivered. NVIDIA's DGX B300 chapter prints the same example, with 200, 1,000 and 700 W, so it gives no separate range for the B300. We found no NVIDIA document that prints the output of nvidia-smi -q -d POWER for a B200 or B300. On a delivered server that command shows the Min, Max and Default Power Limit the driver accepts for each GPU, and those values decide.
NVIDIA adds two sentences on the low end: "Blackwell GPUs typically consume around 300 W, although they can be power‑capped to a minimum of 200 W", and "Even when capped at 200 W, the GPU will report a power draw exceeding 200 W, including at idle." A cap is a ceiling for the controller, not a promise that the reading stays below it at every moment.
Three ways to set a GPU limit: nvidia-smi, SMBPBI, Redfish
nvidia-smi, in-band. NVIDIA's chapter names nvidia-smi as the host channel without giving the syntax. The options are those of NVIDIA's nvidia-smi documentation, described in our article on the RTX PRO 6000 power limit with nvidia-smi: nvidia-smi -q -d POWER to read the range and nvidia-smi -i 0 -pl 700 as root to set a GPU, within its Min and Max Power Limit. That article also shows a systemd unit that sets the limit again at every boot. NVIDIA's DGX chapter does not say whether an nvidia-smi limit on a B200 survives a driver reload, so plan as if it does not.
SMBPBI, out-of-band. The SMBus Post-Box Interface lets the BMC set the limit without the host. Which SMBPBI functions a server's BMC uses is the maker's choice; our article on GPU out-of-band monitoring through the BMC explains the path.
Redfish, through the BMC. NVIDIA documents each baseboard GPU as a Redfish resource under the system HGX_Baseboard_0, as processor GPU_ with an id from 1 to 8, and its Environment. In the output, "the Reading field indicates the current power usage, and the SetPoint field indicates the current GPU power limit", with AllowableMin, AllowableMax and DefaultSetPoint beside them. The Redfish property for the limit is PowerLimitWatts.
A system budget on the DGX B200 and B300 with ipmitool
A GPU limit leaves processors, memory, network cards and fans uncapped. NVIDIA's DGX systems also have a system budget, set through the BMC with IPMI raw commands. The chapter starts from the supplies: "By default, a system will boot with three power supplies", and "To achieve the safe operation of an N+N configuration, you need to enable the power capping feature", which then limits the power the system consumes. The DGX B300 chapter repeats that sentence and the same commands.
| ACTION | COMMAND |
|---|---|
| Read the system limit | ipmitool raw 0x3c 0x80 0x05 |
| Set 6 kW, NVIDIA's example | ipmitool raw 0x3c 0x81 0x05 0x70 0x17 |
| Set 12 kW, NVIDIA's example | ipmitool raw 0x3c 0x81 0x05 0xE0 0x2E |
NVIDIA DGX B200 user guide, "Managing Power Capping", updated 17 October 2026, and DGX B300 user guide, same chapter; read 27 November 2026. NVIDIA's page prints the 12 kW command with "x3c" instead of "0x3c".
The response to the read command has the format "c8 32", which NVIDIA decodes as "(0xc8 + 0x32 << 8) = 0x32c8 = 13000", and "If the feature is disabled, a value greater than 12,000 is returned." The value is in watts with the low byte first; the 6 kW example sends 0x70 0x17 for 0x1770. The template line on the same page writes the two bytes as "<MSB> <LSB>", which contradicts the examples, so check every new value with the read command. By the examples' byte order, a 9 kW limit, 9,000 or 0x2328, would be sent as 0x28 0x23; that is our arithmetic, not an NVIDIA example.
NVIDIA's example of enabling PSU redundancy sets a budget of 12 kW. After the 6 kW cap, the same chapter shows a GPU's Redfish set point at 562 W instead of 700 W; in our reading the BMC passes the system budget down to the GPU limits.
These commands are documented for NVIDIA's DGX systems, which we do not supply. On the model pages of Supermicro, ASUS and Gigabyte that we read for their HGX B200 and B300 servers we found no system power-capping feature, so do not assume the same raw commands work on their BMCs.
NVIDIA's power profiles and Dynamic Power Software
NVIDIA's power profiles set a number of GPU parameters for a type of work in one step. NVIDIA's technical blog of 4 December 2025 says they were released "with NVIDIA Blackwell B200"; the B300 is not named there. The profiles run from Max-Q, for efficiency, to Max-P, for performance, with names such as MAX-Q-Training, and NVIDIA lists Slurm (--power-profile MAX-Q-Training), nvidia-smi, DCGM, Base Command Manager, Redfish and its DGX software Mission Control as ways to apply them. A minimum driver version is not given in what we read. Base Command Manager is included with NVIDIA AI Enterprise, as our guide to Base Command Manager for small GPU clusters describes.
NVIDIA Dynamic Power Software (DPS), documented in a guide updated 20 October 2026, works one level up: "DPS uses Redfish as its primary interface for communicating with NVIDIA DGX compute nodes." Its support list names DGX H100 and H200, DGX B200, DGX B300, GB200 and GB300 NVL systems and Vera Rubin NVL72, and no OEM HGX servers. Its credentials are kept in a Kubernetes secret.
What a power cap costs in throughput
The figures NVIDIA publishes come from B200 systems. NVIDIA's paper "Datacenter Energy Optimized Power Profiles" (arXiv 2510.03872, October 2025) reports "Power savings of up to 15% are achieved with, at most, a 3% performance loss". The blog of 4 December 2025 adds a comparison: plain frequency scaling cost 10 per cent of performance for 5 per cent of data-centre power, the training profiles 1 per cent for 5 per cent and the inference profiles 3 per cent for 8 per cent, while Max-P gained 2 to 3 per cent of performance. For facilities limited by power, the blog reports up to 13 per cent more throughput.
| B200, MAX-Q TRAINING | GPU POWER | SYSTEM POWER | JOB ENERGY |
|---|---|---|---|
| NeMo GPT-3 5B | −4 % | −8 % | −7 % |
| Llama 3 8B | −5 % | −8 % | −6 % |
| Nemotron 22B | −18 % | −12 % | −10 % |
| BERT Large | −16 % | −10 % | −8 % |
NVIDIA, "Datacenter Energy Optimized Power Profiles", arXiv 2510.03872 (October 2025), Table II; NVIDIA's measurements on B200, read 27 November 2026.
For inference, the paper's Table I lists 3 per cent performance loss and 8 per cent throughput gain in a power-constrained setting for DeepSeek R1, and 2 and 6 per cent for Llama 3.1 70B. These are NVIDIA's results for its profiles, not for an arbitrary nvidia-smi limit. We found no published measurement for a fixed per-GPU cap on the B200 or B300, so we give no figure for one. Energy per token, the measure behind these savings, is the subject of our article on GPU energy per token.
The makers' servers: redundancy that depends on load
On the HGX B200 and B300 pages of Supermicro, ASUS and Gigabyte we read, no power-capping line appears. Some pages tie redundancy to the load instead. Supermicro's AMD model AS -8126GS-NB3RT says "Power supply full redundancy based on configuration and application load", and Supermicro's HGX H200 server AS-8125GS-TNHR says that redundancy "depends on configuration and application load". Gigabyte's HGX H200 server G893-SD1-AAX3 states "The system supports 5+3 power redundancy at ambient temperatures up to 30°C"; its HGX B200 and B300 pages carry no such sentence. Ask the maker which load keeps full redundancy for the configuration in the quote, and whether its BMC offers a system budget; the management licences of the three makers are in Supermicro, ASUS and Gigabyte BMC licences.
A 10 kW rack position and why the cap does not size the feed
An HGX B200 server belongs to the 14.3 kW class of the DGX B200, and the eight GPUs alone account for up to 8 kW. To hold such a server at 10 kW, about 4.3 kW has to go, by our arithmetic; taken from the GPUs alone that is about 540 W each, leaving roughly 460 W per GPU if nothing else in the server changes. A system budget at the BMC, where the maker offers one, holds the whole server to the figure; GPU limits alone do not. Our guide to an air-cooled AI server in a 10 kW rack shows which PCIe servers fit such a rack without a cap.
In our judgement a cap is a setting for normal operation, not a basis for the electrical design. An in-band limit only applies once the driver runs and may not survive a driver reload, the makers' servers document no system budget, and NVIDIA ties the DGX system cap to the safe operation of the supplies. Breakers, PDUs and UPS units are therefore sized for the full-load figure, 14.3 kW for the DGX B200 class or Supermicro's 15 kW for its HGX B300 node, as our guide to power cords and PDUs for HGX servers works through; the kW and cooling side is in HGX B200 power consumption and cooling.
We match the server and its supplies to the rack before we quote; tell us the contracted kW, the feeds and whether you train or serve models.
FAQ
What is the power limit of a B200 GPU?
nvidia-smi -q -d POWER shows the range on the delivered server.How do I set a B200 power limit with nvidia-smi?
nvidia-smi -i 0 -pl 700 sets GPU 0 to 700 W, within the Min and Max Power Limit that nvidia-smi -q -d POWER reports. Set it again at every boot, for example with a systemd unit.What is the power cap of a B300?
How does HGX power capping work at system level?
ipmitool raw 0x3c 0x81 0x05 and two bytes, low byte first; NVIDIA's 6 kW example lowers each GPU's set point from 700 to 562 W. The makers' HGX server pages we read document no such feature.Can an HGX B200 server run in a 10 kW rack?
How much performance does power capping cost on a B200?
We supply HGX B200 and HGX B300 servers from Supermicro, ASUS, Gigabyte, Dell, HPE and Lenovo per project, matched to your rack budget. Send us the kW limit, the feeds, the workload and the end user, site and intended use. We reply within one business day.