HGX B300 rack: Supermicro SRS-48UAC-B300SX, SuperCluster B300 and Gigabyte GIGAPOD
Eurokommerz, Vienna, since 2006: Private AI/ML · IT Managed Services · Enterprise Training · AI Hardware & Software
- Supermicro's SRS-48UAC-B300SX is a 48U air-cooled rack with four SYS-822GS-NB3RT servers and 32 B300 GPUs; Supermicro estimates about 60 kW per rack and prints 15 kW at full load per node
- Gigabyte's air-cooled AI-AC-POD for HGX B300 has 72 servers in 18 compute racks, four per rack, up to 70 kW per rack and four 415 V 63 A three-phase PDUs per rack
- The liquid-cooled versions hold eight 4U servers and 64 GPUs per rack; Gigabyte's AI-DLC-Rack lists up to 109 kW and an in-rack CDU of 200 kW, Supermicro a 250 kW CDU
- Rack design, cabling, node and cluster tests and on-site deployment are services the makers describe for their own racks; for Supermicro's 4U liquid-cooled HGX B300 servers a complete rack and onsite service are required
- We supply HGX B300 servers from Supermicro, ASUS, Gigabyte, Dell, HPE and Lenovo per project; the rack itself is the maker's product, and your data-centre staff or colocation provider rack the servers
Supplied by Eurokommerz: HGX B300 servers Request a price →
What an HGX B300 rack from Supermicro or Gigabyte contains
An air-cooled HGX B300 rack from Supermicro or Gigabyte holds four 8U servers with 32 B300 GPUs. Supermicro's SRS-48UAC-B300SX page, read 27 November 2026, lists four SYS-822GS-NB3RT nodes in a 48U rack, about 60 kW per rack and "15kW (full load power draw)" per node; Gigabyte's AI-AC-POD page, read the same day, lists up to 70 kW per rack and four 415 V, 63 A three-phase PDUs. The liquid-cooled racks of both makers hold eight 4U servers and 64 GPUs.
These racks are the makers' products, sold with the makers' own integration and deployment services. What we supply is the server: HGX B300 servers from Supermicro, ASUS and Gigabyte, quoted per project. For one to four servers the rack pages are still worth reading, because they are the only place we found where Supermicro prints a full-load figure for its 8U HGX B300 node and where both makers show how they would power, cool and cable four of them.
For an HGX B300 order we need the end user's company, the installation site and the intended use, and the server maker and NVIDIA review the project before they confirm it; our guide to the end-user certificate for NVIDIA GPUs explains the declaration. Send us these three points and the rack position you have, and we reply with a server configuration that fits it.
Supermicro SRS-48UAC-B300SX, line by line
The SRS-48UAC-B300SX is Supermicro's 48U air-cooled rack for HGX B300. Its page lists the rack, one compute node configuration and the scalable unit (SU) that several such racks form with a networking rack.
| ITEM | AS PRINTED |
|---|---|
| Rack | 48U, 19-inch width, 800 mm × 1200 mm |
| Compute nodes | 4 × SYS-822GS-NB3RT per rack |
| GPUs and CPUs | 32 GPUs and 8 CPUs per rack |
| Power per node | 15 kW, full load power draw |
| Estimated rack power | about 60 kW per rack |
| Compute fabric | up to 12 × Spectrum-4 SN5610, 800GbE |
| Converged network | up to 2 × SN5610 |
| Out-of-band management | up to 4 × Spectrum SN2201, 1/10GbE |
| Scalable unit | 4, 8 or 32 nodes, 32 to 256 GPUs |
| Racks per scalable unit | up to 8 compute, 1 networking |
| Scalable unit totals | up to 73.7 TB HBM3e, up to 500 kW |
Supermicro's SRS-48UAC-B300SX page (undated), read 27 November 2026. The page does not label the axes of "800 mm × 1200 mm" and prints no PDU, cooling or weight line.
Four nodes at 15 kW each make the 60 kW of the rack, and 32 nodes at 15 kW make 480 kW within the 500 kW of the largest SU, by our multiplication. The 73.7 TB of HBM3e are 256 GPUs at Supermicro's 288 GB each; NVIDIA's HGX page prints 2.1 TB for eight GPUs, which would give about 67.2 TB for 256 by our arithmetic. Our review of the Supermicro SYS-822GS-NB3RT explains the two memory figures and lists the server itself.
The switch counts belong to the SU with its networking rack, so the page writes them as "up to"; they are not a count for one rack of four nodes.
Under services, Supermicro lists "Full rack-level design, component installation, and cabling", "System-level testing of each node (L11)", "Cluster-level multi-node testing (L12)" and "Plug-and-play on-site deployment and validation". These are Supermicro's services for its rack.
SuperCluster B300 datasheets: 8U air, 4U liquid and 2-OU OCP
Supermicro's datasheet "SuperCluster B300 Front I/O" (©2025) shows two rack types. The 8U air rack holds four SYS-822GS-NB3RT or AS -8126GS-NB3RT servers with 32 B300 GPUs and 9.2 TB of HBM3e per rack. The 4U liquid rack holds eight SYS-422GS-NB3RT-ALC, SYS-422GS-NB3RT-LCC or AS -4126GS-NB3RT-LCC servers with 64 GPUs and 18.4 TB per rack, cooled through a "Supermicro 250kW capacity Coolant Distribution Unit (CDU) with redundant PSU and dual hot-swap pumps". For a 72-node cluster of 576 GPUs the datasheet lists twenty racks of 48U × 750 mm × 1400 mm and 38 PDUs of "415V/60A 3Ph" for air, and eleven racks of 48U × 800 mm × 1470 mm, 56 PDUs and nine 250 kW CDUs for liquid. It prints no rack kW and no facility water temperature, and the image captions "Air-Cooled" and "Liquid-Cooled" in the copy we read appear swapped against the text.
The third design is the 2-OU SYS-222GS-NB3OT-ALC for 21-inch OCP Open Rack V3. Supermicro's 2-OU datasheet (©2025) states that "a single OCP ORV3 rack supports up to 18 compact 2-OU nodes with 144 GPUs total", powered from "1U 33kW (6x 5.5kW PSUs) power shelves" over a busbar, with a 250 kW in-rack CDU for the 72-GPU rack and a CDU of 1.8 MW capacity for the 144-GPU rack. No rack kW is printed. The nodes share the rack's power shelves over an ORV3 busbar, so by our reading they run only inside such a rack.
Gigabyte GIGAPOD for HGX B300: AI-AC-POD and AI-DLC-Rack
Gigabyte publishes two rack-level offers for HGX B300 under the GIGAPOD name. Both pages were read on 27 November 2026.
| ITEM | AI-AC-POD (AIR) | AI-DLC-RACK (LIQUID) |
|---|---|---|
| Servers | 72 × 8U GPU servers | 8 × 4U DLC GPU servers |
| GPUs | 576 Blackwell Ultra SXM | 64 Blackwell Ultra SXM |
| Racks | 18 + 2, 42U or 48U | one rack, 42U |
| Power per rack | up to 70 kW | up to 109 kW |
| PDUs per rack | 4, 415 V, 63 A, 3-phase | 6, 415 V, 100 A, 3-phase |
| Cooling | air | in-rack liquid-to-liquid CDU, 200 kW |
| Network | validated InfiniBand or Ethernet | space reserved for switches |
Gigabyte's pages "AI-AC-POD NVIDIA HGX B300" and "AI-DLC-Rack NVIDIA HGX B300", read 27 November 2026. "18 + 2" is Gigabyte's count of compute and management racks.
The air pod uses the G894-AD3-AAX7, G894-SD3-AAX7 and G894-ZD3-AAX7, the DLC rack the G4L4-SD3-LAX7 with Xeon 6 and the G4L4-ZD3-LAX7 with AMD EPYC. Seventy-two servers in eighteen compute racks are four servers per rack by our division, the same density as Supermicro's air rack. Gigabyte names no switch models or counts for the air pod, only "Flexible validated InfiniBand / Ethernet switch configurations", and offers its GIGABYTE POD Management software as an option. The DLC rack rates its CDU at "Cooling Capacity: 200 kW (4°C approach temperature)" and adds Gigabyte's G-REX power and cooling management kit with an N120-LS0 management node. Neither page gives a facility water temperature, and we found no on-site service statement on either.
The 8U servers in the air pod are the models in our article on Gigabyte G894 HGX B200 and B300 servers. We did not read the model pages of the G4L4 servers.
Four air-cooled HGX B300 servers per rack: the figures side by side
| ITEM | SUPERMICRO SRS | GIGABYTE AI-AC-POD |
|---|---|---|
| Servers per rack | 4 × 8U | 4 × 8U, by our division |
| GPUs per rack | 32 | 32, by our arithmetic |
| Rack power | about 60 kW, estimated | up to 70 kW |
| Per server | 15 kW full load | not printed |
| PDUs | not printed | 4 × 415 V, 63 A, 3-phase |
| Rack size | 48U, 800 × 1200 mm | 42U or 48U |
Supermicro's SRS-48UAC-B300SX page and Gigabyte's AI-AC-POD page, read 27 November 2026.
Gigabyte's 70 kW divided by four servers is 17.5 kW per server by our division. That is an upper bound for the rack, not a server rating: Gigabyte does not say what else the figure includes. Gigabyte lists twelve 3,000 W supplies for its 8U HGX B300 servers, as 6+6 on the G894-AD3-AAX7, each delivering 3,002.4 W at 220 to 240 V, so the six on one side give about 18 kW by our arithmetic.
What one to four HGX B300 servers take from these racks
Power per server. The 15 kW that Supermicro prints for the SYS-822GS-NB3RT is the first full-load system figure we have found from a maker for an 8U HGX B300 server. It sits next to NVIDIA's 14.5 kW and 15 kW system maximum for the DGX B300. Plan one air-cooled HGX B300 server at 15 kW, two at 30 kW and four at 60 kW, by our multiplication, and size each of the A and B feeds for the whole load. Cords, outlets and feeds per model are in our guide to power cords and PDUs for HGX servers; capping below that figure is in power capping for HGX B200 and B300 servers.
Rack depth. The SYS-822GS-NB3RT is 950 mm deep. Supermicro's single-rack page prints 1200 mm, its cluster datasheet 1400 mm for the air racks; 1200 mm leaves 250 mm behind a 950 mm chassis by our subtraction, before rails, door and the bend of the power cords. Gigabyte's 8U servers are 923 mm deep.
kW per rack. Four servers at 60 to 70 kW are well above the 15 to 40 kW band our guide to GPU rack power and cooling plans for inference racks, and above the roughly 50 kW where that guide sees the practical limit of air with containment. Both makers still design these as air racks; whether your room can cool one is for the facility team to answer. A rack with two servers, about 30 kW, stays inside the inference band.
Switches. Four servers with eight 800G ConnectX-8 ports each bring 32 compute ports, which NVIDIA's enterprise reference architecture for HGX B300 runs as 64 links of 400 Gb/s; on port count alone that is half of one 128-port 400 GbE SN5600, by our arithmetic, plus a converged and a management network. NVIDIA builds that architecture on the same four-server unit. The twelve SN5610 in Supermicro's list serve a 32-node SU. Our article on networking two HGX servers works out the links for two and four servers.
Liquid. If the plan points to the 4U liquid-cooled servers, read the conditions first. Supermicro's 4U HGX B300 models we read, the SYS-422GS-NB3RT-LCC and -ALC, carry "complete rack and onsite service are required" in their titles, and the page of the SYS-422GS-NB3RT-ALC adds "Complete liquid-cooled rack integration is required for purchase". That rack and that onsite service are Supermicro's; our article on liquid-cooled HGX B200 and B300 servers in 4U collects what the makers state about CDUs and coolant.
How HGX B300 servers are quoted when the makers sell racks
We quote HGX B300 servers from Supermicro, ASUS, Gigabyte, HPE and Lenovo per project, on one EU contract and invoice, with warranty and service from the server maker, handled through us. We do not supply racks, PDUs, switches or the makers' rack integration, and we do no work on site. Your data-centre staff or your colocation provider rack and connect the servers; hardware service on site comes from the server maker as configured in the quote. On request we pre-install the operating system, drivers, CUDA and a container runtime, with remote setup by our engineering partner Vixen.UNO.
The questions to ask a data centre before four such servers arrive are in colocation for GPU servers in the EU. For racks of PCIe servers with the RTX PRO 6000 Server Edition, Supermicro publishes a separate design, the SRS-48UAC-RTXPRO, with 8.6 to 9.1 kW per server instead of 15 kW.
Tell us the number of servers, the kW and depth of the rack position and the end user, and we come back with the models and power supplies that fit.
FAQ
What is the Supermicro SRS-48UAC-B300SX?
How many HGX B300 servers fit in one rack?
How many kW does an HGX B300 rack need?
What is Gigabyte GIGAPOD for HGX B300?
Do you supply a complete HGX B300 rack?
What is the difference between the SRS-48UAC-B300SX and the SRS-48UAC-RTXPRO?
We supply HGX B300 servers from Supermicro, ASUS, Gigabyte, Dell, HPE and Lenovo per project, matched to your rack position. Send us the number of servers, the rack's kW and depth, the end user, the site and the intended use. We reply within one business day.
Request a priceWe reply within one business day